ARTDrive V2 series - Instruction Manual Chapter 4 Wiring Procedure • 43
4.2.1 Terminal Assignment on Power Section / Cable Cross-Section
Table 4.2.1.1: Power Section Terminals from 1007 to 3150 (230...480Vac) and 2002 to
3020 (575Vac)
Function (max)
Motor ground connection
Braking unit resistor circuit (braking resistor
must be connected between BR1 and C)
DC link circuit connection
(770 V / 1.65 output current)
DC
AC mains voltage
(see tables 2.3.2.1-A and B)
Motor connection
(AC line volt 3Ph, 1.36 output current)
Braking resistor
(optional)
M
3Ph~
PE1 /
Grounding (protective earth) conductor
U1/L1
V1/L2
W1/L3
BR1
U2/T1
V2/T2
W2/T3
C
D
PE2/
Table 4.2.1.2: Power Section Terminals from 4220 to 81600 (230...480Vac) and 4025 to
8200(575Vac)
Motor ground connection
Braking unit resistor circuit (braking resistor
must be connected between BR1 and C)
AC mains voltage
(see tables 2.3.2.1-A and B)
Braking resistor
(optional)
PE1 /
Grounding (protective earth) conductor
U1/L1
V1/L2
W1/L3
BR1
U2/T1
V2/T2
W2/T3
C
D
PE2/
M
3Ph~
Motor connection
(AC line volt 3Ph, 1.36 output current)
DC link circuit connection
(770 V / 1.65 output current)
DC
Function (max)
Power terminals lay-out
Sizes 1007 to 3150 (230...480Vac) and 2002 to 3020 (575Vac):
the terminals of the devices are made accessible by removing the cover and the
cable entry plate (see section 4.1, “Accessing to the connectors”). All the power
terminals are located on the power card.
The terminal strip itself is a removable connector.