44 • Chapter 4 Wiring Procedure ARTDrive V2 series - Instruction Manual
Sizes 4220 to 81600 (230...480Vac) and 4025 to 8200 (575Vac):
the terminals of the devices are made accessible by removing the cover (see
section 4.1, “Accessing to the connectors”).
Maximum Cable Cross Section for Power Terminals
AC input wiring is connected to a disconnected switch, which limits the size to
the following ranges:
AVy…-4 (230…480Vac) type 1007 1015 1022 1030 2040 2055 2075 3110 3150 4220 4300
AWG
12 8 4
[mm2]
8 101625
Tightening torque
[Nm]
23
AWG
12 8 6 10 8
[mm2]
810610
Tightening torque
[Nm]
0.9 1.6
AWG
12 8 6
[mm2]
8 101616
Tightening torque
[Nm]
23
AVy…-4 (230…480Vac) type 4370 5450 5550 6750 7900 71100 71320 81600
AWG
1/0 2/0 4/0 300* 350* 4xAWG2 * = kcmils
[mm2]
50 70 95 150 185 4x35
Tightening torque
[Nm]
AWG
8
[mm2]
10
Tightening torque
[Nm]
1.6
AWG
[mm2]
Tightening torque
[Nm]
3
AVy…-5 (575Vac) Type 2002 2003 2005 3007 3010 3015 3020 4025 4030
AWG
[mm
2
]
Tightening torque
[Nm]
AWG
[mm
2
]
Tightening torque
[Nm]
AWG
[mm
2
]
Tightening torque
[Nm]
AVy…-5 (575Vac) type 4040 5050 5060 5075 6100 7125 7150 8200
AWG
6 4 1/0 2/0 4/0 350* * = kcmils
[mm
2
]
16 25 50 70 95 185
Tightening torque
[Nm]
2 4 12 12 10-30
AWG
10 6
[mm
2
]
616
Tightening torque
[Nm]
0.9 3
AWG
[mm
2
]
Tightening torque
[Nm]
avy4040
2
2
50
4 12 10-30
U1,V1,W1,U2,V2,W2,C,D
terminals
PE1, PE2 terminals
U1,V1,W1,U2,V2,W2,C,D
terminals
PE1, PE2 terminals
BR1 terminals
BR1 terminals
14
2
610
4
0.5to0.6
6
1.2to1.5
14 10
24
0.5to0.6 1.2to1.5
14
2
terminals not available
35
10
4
6
16
1.2to1.50.5to0.6
3
U1,V1,W1,U2,V2,W2,C,D
terminals
14 10
6
16
4
8
248
0.5to0.6 1.2to1.5 2
BR1 terminals
14 10 8 10
2486
0.5to0.6 1.2to1.5 0.9
PE1, PE2 terminals
14 10 8 6
24816
0.5to0.6 1.2to1.5 2
U1,V1,W1,U2,V2,W2,C,D
terminals
2
35
2
4
BR1 terminals
PE1, PE2 terminals
6
16
6
16
2
terminals not available
2
50
4
NOTE! Use 60°C / 75°C copper (CU) conductor only.