MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 109
B STARTUP
The drive can control the motor in three different ways: V/f (VF), Field Oriented (FOC)
and Sensorless vect (SLS).
Start the process for the motor data automatic measuring.
• Automatic calculation of the flux and current loop gains according to the performed
measuring processes.
• Setting of the information about:
- maximum speed
- configuration of the V/f mode.
- drive parameters (mains voltage, ambient temperature, etc.)
- motor parameters
- inverter main commands
- inverter main reference
- motor/inverter ramp times
- encoder features, if used.
- parameters of the I2t protections.
Such settings can be changed only with a disabled drive. While in this operation mode
(Configuration) the data updating on the terminal strip and on the option cards is stopped.
B00 STARTUP / Drv & Mot config
After downloading drive parameters from a file, or entering the STARTUP / Drv & Mot
config menu through the keypad, the drive restart is only permitted after:
a) cycling drive power
or:
b) when Commands select = Terminal level, cycling input DI0,
when Commands select = Terminal edge, cycling input DI0, and the digital input
selected by Term strstp src,
when Commands select = Digital level, cycling the digital signals selected by
Digital strstp src and Digital enable src
when commands select = Digital edge, cycle input DI0 or the digital input Digital
enable src (if not selected to ONE), and the digital signal selected by Digital
strstp src.
It allows to select the desired regulation mode. After choosing the setting, the Drive
carries out the restart phase by setting the selected regulation mode.
B0A STARTUP / Drv & Mot config / Regulation mode
B0A.00 Regulation mode N/A R 0 0/7 DK V-F-S Easy 100
It allows to select the desired regulation mode. When the Regulation mode parameter is
selected, the active regulation mode is displayed; in order to change it to a new mode
press “Enter”; then scroll the list:
[1] V/f control V/f scalar control
[2] FOC control Field Oriented control
[3] SLS control Sensorless control