Index MENU [Unit] Access Default Min/Max Format Reg.Mode Level Ipa
Parameter Name
Description
Chapter 6 Parameter • 110 ARTDrive V2 series - Instruction Manual
B0B STARTUP / Drv & Mot config / Drv data
B0B.00 Mains voltage [V] RW (*) 0/7 DK V-F-S-B Easy 380
The Voltage selections available are:
[0] 230 V
[1] 380 V
[2] 400 V (*) Default for 400V Europe
[3] 415 V
[4] 440 V
[5] 460 V (*) Default for 460V American
[6] 575 V (*) Default for 575V American
Drive power supply voltage. Select supply voltage parameter accurately, according to
actual drive supply voltage. After changing this parameter, selftune data are initialized to
default, self-tuning must be repeated !
B0B.01 Switching freq [kHz] RW D.Size 0/3 DK V-F-S-B Easy 170
[0] 2 kHz
[1] 4 kHz
[2] 8 kHz
[3] 16 kHz
Drive PWM switching frequency. Selecting higher switching frequency then default,
results in drive derating, see table 2.3.2.1-A or 2.3.2.1-B.
Selecting lower value results in higher continuous output current.
After changing this parameter, selftune data are initialized to default, self-tuning must be
repeated !
B0B.02 Ambient temp [°C] RW 0 0/1 DK V-F-S-B Full 1350
[0] 40°C
[1] 50°C
Drive ambient temperature. Selecting 50°C will result in drive derating, see paragraph
2.3.1.
After changing this parameter selftune data are initialized to default, self-tuning must be
repeated !
B0C STARTUP / Drv & Mot config / Full scale speed
B0C.00 Full scale speed [rpm] RW 1500 Calc/Calc PV V-F-S-B Easy 1885
It defines the 100% of the application speed referenced. The absolute speed handling
range is ± 200% Full scale speed.
For all application set this parameter to maximum allowed motor speed, typically rated
speed of the motor.
This parameter will also set the limit on all multispeed values.
NOTE! If the parameter setting changes exceed one of the interval listed below, Motor
Autotune procedure must be repeated.