ARTDrive V2 series - Instruction Manual Chapter 5 Quick Start Up Guide • 85
5.5 Quick Start-up Procedure
Step
Operation
Go to the menu B STARTUP
If required:
set drive regulation
mode (defult is
[1] V/f control)
If required:
set the drive main voltage
Default are:
- [5] 460V for AVy...-4A
- [6] 575V for AVy...-5
Set the drive
maximum reference speed
Set the motor rated
voltage
Set the motor rated
frequency
Set the motor rated
current
Set the motor rated
speed
Set the motor rated
power (kW)
Set the motor power
factor (cosphi)
Description
Scroll drive menus using t key, until STARTUP menu.
B STARTUP / B00 Drv & Mot config
Enter the B0A.00 - Regulation mode parameter
to set a different regulation mode: [1] V/f control,
[2] FOC control and [3] SLS control .
B STARTUP / B0B Drv data
Enter the B0B.00 - Mains voltage parameter
to set the drive main voltage ([0] 230V, [1] 380V,
[2] 400V, [3] 415V, [4] 440V, [5] 460V and [6] 575V).
B STARTUP / B00 Drv & Mot config / B0C Full scale speed
Enter the B0C.00 - Full scale speed parameter, which
defines the 100% of the application speed referenced.
Absolute speed handling range is ±200% of B0C.00.
B STARTUP / B00 Drv & Mot config / B0D Mot data
Enter the B0D.00 - Motor rated volt parameter
to set the motor rated voltage (*).
B STARTUP / B00 Drv & Mot config / B0D Mot data
Enter the B0D.01 - Motor rated freq parameter
to set the motor rated frequency (*).
B STARTUP / B00 Drv & Mot config / B0D Mot data
Enter the B0D.02 - Motor rated curr parameter
to set the motor rated current (*).
B STARTUP / B00 Drv & Mot config / B0D Mot data
Enter the B0D.03 - Motor rated speed parameter
to set the motor rated speed (*): if Slip data is available(*)
B0D.03 = Synchronous speed - Slip
B STARTUP / B00 Drv & Mot config / B0D Mot data
Enter the B0D.04 - Motor reted power parameter
to set the motor rated power (*).
Note! kW = Motor Hp rating * 0.736
B STARTUP / B00 Drv & Mot config / B0D Mot data
Enter the B0D.05 - Motor power fact parameter
to set the motor power factor (*).
(*): nameplate data