ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 235
HFLUX
FLUX / Flux maximum
NOTE! Menu accessible with Access Level = FULL
This function allows the user to control the maximum value of the Flux current.
The function is linked to the control of the voltage loop.
In a condition where the Flux is = 0, the voltage regulator prevails by controlling the
motor. It means that it is only possible to further limit the requirement of the voltage loop.
In case the drive is active in the constant torque area, it is possible to set an overflux up
to 115% of the rated flux.
This is possible, obviously, only if the motor/drive combination is in a position to
supply a sufficient magnetizing current.
The H00.00 - Flux level src source allows to select the function control signal, which is
standard connected to H00.10 - Dig Flx MaxLim parameter.
NOTE! The Function is active only in a Sensorless and Field oriented mode.
H00 FLUX / Flux max
H00.00 Flux level src N/A RWS Ipa1120 Plist24 PIN F-S-B Full 1121
Ipa 1120 - Dig Flx MaxLim= Default
It select the origin of the signal that determine the maximum Flux level value.
ªª
ªª
ª
Pick List 24
H00.10 Dig Flx MaxLim [%] RWS 100 60/Calc PV F-S-B Full 1120
Internal digital value of maximum Flux level
H00.11 Inuse flx maxlim [%] R 0.00 0.00/- PV F-S-B Full 1150
Displaying of Flux level signal