Chapter 6 Parameter • 236 ARTDrive V2 series - Instruction Manual
FLUX / Magnetizing configuration
The function is active only in a Sensorless and Field oriented mode and is useful for
undesired motor shaft rotation.
It allows to lock the flux position, Lock flux, and to set a Ramp time of the magnetizing
current H01.00 - Magn ramp time.
In the configurations it is possible to start the Lock flux function. Via the H01.01 - Lock
flux pos parameter, it is possible to lock the flux position when the following selected
condition is satisfied:
· Off non-active function
· At magnetization during magnetization
· At Spd=0 with Speed 0 delay signal
· At magn & Spd=0 during magnetization and with a Speed 0 delay signal
· At magn and Ref=0 during magnetization and Ref 0
· At Ref=0 with Reference 0
NOTE! In order to have a better performances of Autocapture (Catch on Fly) function, it is
recommended to set H01.01 - Lock flux pos = At Ref = 0.
Furthermore, in H01.00 - Magn ramp time it is possible to set the magnetizing current
ramp time in seconds, which can be used:
To slow down the temporary magnetizing period and avoid a rotation of the motor
shaft due to the stator-rotor alignment
To speed up the magnetizing phase
H01 FLUX / Magn cfg
H01.00 Magn ramp time [sec] RWS DrvSize 0.01/5.00 PP F-S-B Easy 1810
Magnetizing current ramp time.
H01.01 Lock flux pos N/A RWSZ (*) 0/5 DP F-S-B Easy 1815
It is allows to lock the flux position when the following selected condition is satisfied (see
descriptions above):
[0] Off
[1] At Magnetiz
[2] At Spd=0
[3] At Magn&Spd=0
[4] At Magn&Ref=0
[5] At Ref=0
NOTE! For Autocapture function in Sensorless reg. mode, enabling of Autocapture (Catch
on Fly) function if required and H01.01 - Lock flux pos parameter must be set at
“Ref = 0”