ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 191
REF&RAMP / Jump Ref
The block function operates the motor while avoiding resonance caused by characteristic
frequency references in the customer system machine.
Parameters function allow to set two jump reference frequencies in rpm, with their related
jump bandwidth in rpm too. During motor running at constant-speed, operation within
jump reference frequency [rpm] range is prohibited.
Jump ref 2
Freq Reference In
Freq ReferenceOut
Jump ref1
Jump Band 1 or
Jump Band 2
Jump Band 2
Jump Band 2
Jump Band 1
Jump Band 1
Figure D11: Jump frequencies
D11 REF&RAMP / Jump Ref
D11.00 Jump Ref 1 [rpm] RWS 0 0/FSS PP V-F-S-B Easy 345
Jump reference 1 frequency in rpm.
Maximum value setting allowed is equal to B01.00 - Full scale speed (Ipa 1885)
D11.01 Jump Band 1 [rpm] RWS 0 0/(**) PP V-F-S-B Easy 346
Jump bandwidth 1 frequency in rpm.
(**) Maximum value setting allowed is equal to:
a) 100 if Full Scale Speed >100
b) FSS if Full Scale Speed <100
FSS = B01.00 - Full scale speed (Ipa 1885)
D11.02 Jump Ref 2 [rpm] RWS 0 0/FSS PP V-F-S-B Easy 347
Jump reference 2 frequency in rpm.
Maximum value setting allowed is equal to B01.00 - Full scale speed (Ipa 1885).