ARTDrive V2 series - Instruction Manual Chapter 6 Parameter • 205
REG PARAM / Tst Gener
NOTE! Menu accessible with Access Level = FULL
The tuning of the regulators is performed via an internal test signal generator in order to
evaluate the regulator response. This operation requires the use of a digital oscilloscope.
The “Test generator” generates signal shaped as a rectangular wave with a
programmable frequency and amplitude.
Using the Test generator function it is possible to carry out the manual tunings of:
• Current regulator
• Flux regulator
• Voltage regulator
• Speed regulator.
Refer to the chapter 7, Manual Tunings”.
E09 REG PARAM / Tst Gener
E09.00 Test gen mode N/A RWS 0 0/6 DK V-F-S-B Full 2756
This parameter defines where the test signal is connected in the control scheme. In order
to change it to new mode press [Enter], “Select new mode” will be displayed, then scroll
the list.
[0] Off Function disabled
[1] Ramp ref 1 Ramp reference 1
[2] Speed ref 1 Speed reference 1
[3] Torque ref 2 Torque reference 2
[4] Magncurr ref Magnetizing current reference
[5] Flux ref Flux reference
[6] Outvlt lim Voltage reference
E09.01 Gen Hi ref [cnt] RWS 0 -32767/32767 PV V-F-S-B Full 2745
Value in count of the higher amplitude signal value.
E09.02 Gen Low ref [cnt] RWS 0 -3276/ 32767 PV V-F-S-B Full 2750
Value in count of the lower amplitude signal value.
E09.03 Gen Period [sec] RWS 10 0/10000 PV V-F-S-B Full 2755
Period of the square wave.
E09.04 Gen output [cnt] R 0.00 0.00/0.00 PV V-F-S-B Full 2760
Monitoring the test generator output signal.