22 • Chapter 2 Inspection Procedure,... ARTDrive V2 series - Instruction Manual
Table 2.3.2.1-B: AC Input/Output Specifications for 575Vac series
2002 2003 2005 3007 3010 3015 3020 4025 4030 4040 5050 5060 5075 6100 7125 7150 8200
350 x
569 x
509 x 921
x 297.5
t.b.d.
Inverter Output (IEC 146 class1), Continuous service
[kVA]
3.8 4.5 7.0 10.8 13.7 18.6 24.1 30 36 46 58 69 86 109 136 157 210
Inverter Output (IEC 146 class2), 150% overload for
60s
[kVA]
3.4 4.1 6.3 9.8 12.5 16.9 21.9 27 33 42 53 63 78 99 124 143 191
P
N
mot (recommended motor output):
@U
LN
=575Vac; f
SW
=default; IEC 146 class 1
[Hp]
2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200
@U
LN
=575Vac; f
SW
=default; IEC 146 class 2
[Hp]
2 3 5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 200
U
2
Max output voltage
[V]
f
2
Max output frequency (*)
[Hz]
I
2N
Rated output current :
@U
LN
=575Vac; f
SW
= default; IEC 146 class 1
[A]
3.8 4.5 7.0 10.8 13.8 18.7 24.2 30 36 46 58 69 86 109 137 158 211
@U
LN
=575Vac; f
SW
=default; IEC 146 class 2
[A]
3.4 4.1 6.4 9.8 12.6 17.0 22.0 27 33 42 53 63 78 99 125 144 192
f
SW
switching frequency (Default)
[kHz]
2
f
SW
switching frequency (Higher)
[kHz]
2
Iovld
(short term overload current, 200% of I
2N
for 0.5s on 60s)
[A]
7.0 8.2 12.8 19.6 25.2 34.0 44.0 54 66 84 106 126 156 198 249 288 384
Derating factor:
K
T
for ambient temperature
K
F
for switching frequency
0.87 0.64 0.87 t.b.d.
U
LN
AC Input voltage
[V]
AC Input frequency
[Hz]
I
N
AC Input current for continuous service :
- Connection with 3-phase reactor
@ 575Vac; IEC 146 class1
[A]
3.8 4.7 7.4 11.7 15 19.8 25.9 31 35 46 60 68 85 114 146 163 220
- Connection without 3-phase reactor
@ 575Vac; IEC 146 class1
[A]
5.3 6.1 9.9 17 20.7 27.6 33.9
Max short circuit power without line reactor (Zmin=1%)
[kVA]
380 450 700 1080 1370 1860 2410 3000 3600 4600 5800 6900 8600
10900 13700 15700 21000
[V]
[V]
ai2010
I
N
P
U
T
Type
O
U
T
P
U
T
151.5 x 306.5 x 199.5
Mechanical dimension L xHxD(mm)
0.98 x U
LN
(AC Input voltage)
0.7 for higher f
SW
418 x 605 x 320
0.7 for higher f
SW
Braking IGBT Unit (standard drive)
Overvoltage threshold
Undervoltage threshold
Standard internal (with external resistor); Braking torque
150%
External braking unit (optional)
Opt. Int. (with ext. res);
Br. trq 150%
For these types DC choke is inside
8
0.8 @ 50°C (122°F)
1000 V
DC
565 V
DC
(for 575 V
AC
mains)
500 -10% / 575V +10%...- 10% , 3Ph
50/60 Hz ±5%
4
t.b.d.
200
350 x 569 x 268208x323x240
509x1113x
297.5
400
8
16
4