46 • Chapter 4 Wiring Procedure ARTDrive V2 series - Instruction Manual
Table 4.3.1.3: Jumpers on Regulation Card RV33
Designation Function Factory setting
S0 The setting must not be changed OFF
S1 The setting must not be changed ON
S3 Factory use, the setting must not be changed -
S5 - S6 Terminating resistor for the serial interface RS485 ON (*)
ON= Termination resistor IN
OFF= No termination resistor
S8
Adaptation to the input signal of analog input 1 (terminals 1 and 2)
OFF
ON=0...20 mA / 4...20 mA
OFF=0...10V/-10...+10 V
S9
Adaptation to the input signal of analog input 2 (terminals 3 and 4)
OFF
ON=0...20 mA / 4...20 mA
OFF=0...10V/-10...+10 V
S10
Adaptation to the input signal of analog input 3 (terminals 5 and 6)
OFF
ON=0...20 mA / 4...20 mA
OFF=0...10V/-10...+10 V
S11 - S12 - S13 Encoder setting ( jumpers on kit EAM_1618 supplied with the drive) OFF
S14 - S15 - S16 ON=Sinusoidal SE or SESC encoder
(**) OFF=Digital DE or DEHS encoder
S17 Monitoring of the C-channel of the digital encoder OFF
(**)
ON=C-Channel monitored
OFF=C-Channel not monitored (required for single-ended channels)
S18 - S19 Encoder setting B
S20 - S21 Pos. B=digital DEHS encoder
(**) Pos. A= sinusoidal SESC encoder
S22 - S23 Analog input 3 enabling (alternative with SESC encoder) B
(**) Pos. A= if SESC encoder is used
Pos. B=analog input 3 enabled
Pos. OFF= resolver
S24 Jumper to disconnect0V(of24V)fromground ON
ON=0 V connected to ground
OFF=0 V disconnected from ground
S25 Jumper to disconnect 0 V (regulation section) from ground ON
ON=0 V connected to ground
OFF=0 V disconnected from ground
S26 - S27 (**) Resover use enabling ON
Pos. ON=when resolver is not used
Pos. OFF=resolver
S28
Encoder Internal power supply selection
ON/ON=+5V
OFF/OFF=+8V
ON/ON
S29 Internal use A
S30
Second encoder qualifier input
A=from EXP-… board
B=from digital input "6" on RV33-3
A
ay4060
NOTES! (*) on multidrop connection the jumper must be ON only for the last drop of a
serial line.
(**) see table 3.4.2.2 for more details on S11 ... S23 jumper settings.
The devices are factory set accordingly.
When fitting a regulation card as a spare, remember to set again the
encoders jumpers.