80 • Chapter 5 Quick Start Up Guide ARTDrive V2 series - Instruction Manual
Control [Text reference] - Function
keys
[START]
Start key command used to start the drive via keypad; C00.20 - Commands select = [4] I/
O keys parameter setting and +24V between 12 & 13 terminals are always required to
initiate a start/stop command from keypad.
[STOP]
Stop key command used to stop the drive via keypad; C00.20 - Commands select = [4] I/
O keys parameter setting and +24V between 12 & 13 terminals are always required to
initiate a start/stop command from keypad.
Pressing this key for 2 sec, the drive will be disabled. STOP key also resets the sequencer
after an alarm event. The action of the STOP key can be programmed with C00.24 - Stop
key mode parameter, which depending by the setting of C00.20 parameter too:
C00.20 = [4]: (default configuration) main commands are coming from keypad. Therefore,
the STOP key will cause a normal stop of the motor.
- C00.20 ≠ [4] and C00.24 = [0], pressing the STOP key will have no effect.
- C00. 20 ≠ [4] and C00.24 = [1], pressing the STOP key, the motor will execute an
Emergency stop, following the ramp programmed by B03.02 (or D02.02). After the speed
reaches the zero values, the drive will trip with the dedicated alarm “ Key Em Stp fault”. An
alarm reset will be needed to restore drive operations.
Jog
[Increase] / [Jog]
Plus key increases the speed reference for Motor pot function. After pressing shift key,
holding this key causes the drive to Jog (default direction = forward = CW).
[Decrease] / [Rotation control]
Minus key decreases the speed reference for Motor pot function.
After pressing shift key, this key toggles motor rotation direction in Jog mode and Motor pot
function.
Help
[Down arrow] / [Help]
Used to scroll down menu items in menu navigation, picklists in selectors, or digit values in
numeric editing.
After pressing shift key, an item-specific information menu is entered when applicable.
Help menu can be browsed with up/down arrows. Left arrow returns to normal mode.
Alarm
[Up arrow] / [Alarm]
Used to scroll up menu items in menu navigation, picklists in selectors, or digit values in
numeric editing. After pressing Shift key, the Alarm list display mode is entered. Active
alarms and Alarms pending for acknowledge can be browsed with up/downs arrows. Alarms
can be acknowledged whit the Enter key. Left arrow returns to normal mode.
Escape
[Left arrow] / [Escape]
Used to go up one level in menu navigation; to scroll digits in numeric edit mode, to return
to normal mode from alarm list or help modes.
After pressing shift key, it is used to Escape out of numeric edit or selection with no change.
Home
Enter
[Enter] / [Home]
Used to go down one level in menu navigation; to enter selections or numeric values after
editing, to issue commands, to acknowledge alarms in the Alarm list mode.
Home second function is not implemented.
Shift
[Shift]
Shift button enables the keypad second functions (Rotation control, Jog, Help, Alarm,
Escape, Home).