5.2 PT and CT Setting (Examples of Changing the Digits and Moving the Decimal Point)
────────────────────────────────────────────────────
NOTE
3. Set the PT ratio.
To change the numerical value
Press the ▲ or ▼ key 5 times to set to "6".
To change the flashing to decimal point
Press the key 4 times.
To move the decimal point
Press the ▲ key once or press the ▼ key 3 times to set to "60.00".
(4) Set the CT ratio to 400.
1. Press the key once, the flashing point moves to the top of the CT ratio.
2. Set the CT ratio.
To change the numerical value
Press the ▲ key 3 times to set to "4".
To change the flashing to decimal point
Press the key 4 times.
To move the decimal point
Press the ▼ or ▲ key twice to set to "400.0".
3. Press the
ENTER
key to decide the settings ("SC" indicator lit)
If you switch to a different setting display or return to the normal
measurement state while this is flashing, the PT and CT ratios remain at
their previous settings.