7.2 Displaying Trends
115
Chapter 7 Monitoring Fluctuations in Measured Values
(TIME PLOT Screen)
7
Displayed items and channels
Allows you to select the displayed item and channel. Which channels
are available depends on the selected displayed item.
For Freq, Uunb, Iunb, and Eff you can select a detaile
d measurement item, rather than a channel.
AVG indicates the average value for channels 1 through 3 (varies with connection).
Sum indicates the sum for channels 1 through 3 (varies with connection).
CH4 for S, Q, and PF can only be selected when CH4
is set to AC+DC. These values cannot be
selected when CH4 is set to OFF for Eff.
Changing the displayed items, channels, waveforms, or measured
value ([1-Screen] and [2-Screen] screen)
Display the
pull-down menu
Select a setting
Accep setting
Cancel
[Select]
Select
Flag
Indicates that a dip, swell, or interruption oc-
curred during the displayed TIME PLOT inter-
val based on IEC61000-4-30 flag conversion.
A flag indicates that integrated values may be
unreliable.
See: "Flags" (p.120)
Setting Contents:( : Default setting)
Displayed item Displayed channel Displayed item Displayed channel
Freq Freq
f10s Ipk-
CH1
CH2 CH3 CH4
Urms
CH1
CH2 CH3 CH4 AVG Idc
CH4
Upk+
CH1
CH2 CH3 CH4 Iunb
unb
unb0
Upk-
CH1
CH2 CH3 CH4 IharmH
CH1
CH2 CH3 CH4
Udc
CH4
Ithd
CH1
CH2 CH3 CH4
Uunb
unb
unb0 P
CH1
CH2 CH3 CH4 sum
UharmH
CH1
CH2 CH3 CH4 S
CH1
CH2 CH3 CH4 sum
Uthd
CH1
CH2 CH3 CH4 Q
CH1
CH2 CH3 CH4 sum
Irms
CH1
CH2 CH3 CH4 AVG PF
CH1
CH2 CH3 CH4 sum
Ipk+
CH1
CH2 CH3 CH4 KF
CH1
CH2 CH3 CH4
Eff
Eff1
Eff2