13.3 Screen Specifications
220
For current (RMS value, inrush current, and peak current), when the reference value (measured value) is 10% or less of the range, 10%
of the range is used as the threshold value, and when the reference value (measured value) exceeds 100% of the range, 100% of the
range is used as the threshold value.
When the RMS voltage is less than 3% f.s. of the range, 5% of the
range is used as the upper limit, and 0% of the range is used as the
lower limit. When the voltage peak value is less than or equal to 3% f.s. of the range, 5% of the range is used as the threshold value.
For total harmonic voltage and current distortion as well as harmon
ic voltage, functionality is disabled when the measured value (volt-
age RMS value or current RMS value) is less than or equal to 3% f.s. of the range.
If VT or CT is changed after simple configuration (including when
changed outside of the simple configuration process), the threshold
and sense values will not change. (Either repeat simple configuration or reconfigure the event threshold values after setting VT and CT.)
As a rule, settings not included in the table are set to OF
F (other than manual events).
Un = nominal voltage (Uref)
Current unbalance
factor (zero-phase,
negative-phase)
OFF, OFF OFF, OFF OFF, OFF OFF, OFF OFF, OFF
Harmonic voltage
fundamental wave
order 0
Harmonic
orders 3, 5, 7, 9 11
OFF
OFF
OFF
OFF
5% of nominal
voltage
10% of nominal
voltage
OFF
OFF
OFF
OFF
OFF
OFF
As per EN50160
harmonic voltage
limit value; see table
below.
Harmonic current
fundamental wave
order 0
Harmonic
orders 3, 5, 7, 9, 11
OFF
OFF
OFF
OFF
5% of range
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Harmonic power
fundamental wave
order 0
Harmonic
orders 3, 5, 7, 9 11
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
Harmonic voltage and
current phase difference
OFF OFF OFF OFF OFF
Total harmonic voltage
distor
tion factor
5% 7% OFF OFF OFF
Total harmonic current
distortion factor
OFF OFF OFF OFF OFF
K factor OFF OFF OFF OFF
OFF
High-order harmonic
voltage component
OFF OFF OFF OFF OFF
High-order harmonic
cu
rrent component
OFF OFF OFF OFF OFF
Voltage waveform
comparison
±15% ±10% OFF OFF OFF
(7) Easy settings
Abnormal voltage
detection
Basic power supply
quality measurement
Inrush current
measurement
Measured value
recording
EN50160
Setting
Pattern
EN50160 harmonic voltage limits
Odd harmonics Even harmonics
Not multiples of 3 Multiples of 3
Order h Relative voltage (Un) Order h Relative voltage (Un) Order h
Relative voltage (Un)
5 6.0% 3 5.0% 2 2.0%
7 5.0% 9 1.5% 4
1.0%
11 3.5% 15 0.5% 6...24 0.5%
13 3.0% 21 0.5%
17 2.0%
19 1.5%
23 1.5%
25 1.5%
HIOKI PQ3198A961-02