A13
Appendix
TIME PLOT screen (detailed trends)
SYSTEM_DF1 [Record] TIME PLOT Interval (setting period)
Approx. 200 ms aggregation (50 Hz: 10 cycles, 60 Hz: 12 cycles)
Voltage RMS value is calculated for one
waveform shifted over half a wave.
Example:
There are 24 calculated U (Urms1/2) values
in an approx. 200 ms aggregation at 60 Hz
(12 cycles).
RecordingRecording
Example:
when interval:1min,
N=7200
Event Waveform Recording Method
Generating events using approx. 200 ms aggregation measured values
RMS calculation RMS calculation RMS calculationEVENT occur
Event waveform record-
ing period
50 Hz: 14 cycles
60 Hz: 16 cycles
The result of adding the two waveforms
prior to and the two waveforms after the
approx. 200 ms aggregation is displayed
as the event waveform.
Approx. 200 ms aggregation (50 Hz: 10 cycles, 60 Hz: 12 cycles)
SYSTEM_DF1 [Record] TIME PLOT Interval (setting period)
Generating events using one- or half-wave measured values
SYSTEM_DF1 [Record] TIME PLOT Interval (setting period)
Approx. 200 ms aggregation (50 Hz: 10 cycles, 60 Hz: 12 cycles)
Event waveform record-
ing period
50 Hz: 14 cycles
60 Hz: 16 cycles
The result of adding the two waveforms
prior to and the two waveforms after the
approx. 200 ms aggregation is displayed
as the event waveform.
HIOKI PQ3198A961-02