EasyManuals Logo

Hirschmann RS20 User Manual

Hirschmann RS20
294 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #113 background imageLoading...
Page #113 background image
Synchronizing the System Time in the
Network
Basic Configuration
Release
6.0
07/2010
7.3
Precision Time Protocol
113
The following configuration steps apply to the device with the IP address
10.0.1.112. Configure the other devices in the same way with the values from
the table above.
Enter the SNTP parameters.
Device 10.0.1.112 10.0.1.116 10.0.1.105 10.0.1.106
PTP Global
Operationonononon
Clock Mode v1-boundary-
clock
v1-boundary-
clock
v1-simple-mode v1-simple-mode
Preferred Master true false false false
SNTP
Operation on off off off
Client Status on off off off
External server
address
10.0.1.2 0.0.0.0 0.0.0.0 0.0.0.0
Server request
interval
30 any any any
Accept SNTP
Broadcasts
No any any any
Server status on off off off
Anycast destination
address
0.0.0.0 0.0.0.0 0.0.0.0 0.0.0.0
VLAN ID1111
Table 9: Settings for the example (see fig. 31)

Table of Contents

Other manuals for Hirschmann RS20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hirschmann RS20 and is the answer not in the manual?

Hirschmann RS20 Specifications

General IconGeneral
MountingDIN Rail
Operating Temperature-40°C to +70°C
Protection ClassIP30
Switching TechnologyStore-and-Forward
Product TypeIndustrial Ethernet Switch
Port Details10/100 Mbps Ethernet ports
Switching Capacity3.2 Gbps
MAC Address Table8k
ManagementWeb, SNMP
RedundancyMRP
Ports8 or 16

Related product manuals