Operation Diagnosis
184
9.3
Out-of-band Signaling
Basic Configuration
Release
6.0
07/2010
9.3 Out-of-band Signaling
The signal contact is used to control external devices and monitor the
operation of the device. Function monitoring enables you to perform remote
diagnostics.
The device reports the operating status via a break in the potential-free signal
contact (relay contact, closed circuit):
X Incorrect supply voltage,
at least one of the two supply voltages is inoperative,
the internal supply voltage is inoperative.
X The temperature threshold has been exceeded or has not been reached.
X The removal of a module (for modular devices).
X The removal of the ACA.
X The configuration on the ACA does not match that in the device.
X The interruption of the connection at at least one port. In the Basic
Settings:Port Configuration menu, you define which ports the
device signals if the connection is down (see on page 74 “Displaying
connection error messages“). On delivery, there is no link monitoring.
X Event in the ring redundancy:
Loss of the redundancy (in ring manager mode). On delivery, there is no
ring redundancy monitoring.
X Event in the ring/network coupling:
Loss of the redundancy. On delivery, there is no ring redundancy
monitoring.
The following conditions are also reported by the device in standby mode:
– Defective link status of the control line
– Partner device is in standby mode
X Failure of a fan (MACH 4000).
Select the corresponding entries to decide which events the device status
includes.
Note: With a non-redundant voltage supply, the device reports the absence
of a supply voltage. If you do not want this message to be displayed, feed the
supply voltage over both inputs or switch off the monitoring (see on page 185
“Monitoring the Device Status via the Signal Contact“).

Table of Contents

Other manuals for Hirschmann RS20

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hirschmann RS20 and is the answer not in the manual?

Hirschmann RS20 Specifications

General IconGeneral
MountingDIN Rail
Operating Temperature-40°C to +70°C
Protection ClassIP30
Switching TechnologyStore-and-Forward
Product TypeIndustrial Ethernet Switch
Port Details10/100 Mbps Ethernet ports
Switching Capacity3.2 Gbps
MAC Address Table8k
ManagementWeb, SNMP
RedundancyMRP
Ports8 or 16

Related product manuals