EasyManuals Logo
Home>Honeywell>Control Systems>AUTOMATIC CONTROL SI Edition

Honeywell AUTOMATIC CONTROL SI Edition User Manual

Honeywell AUTOMATIC CONTROL SI Edition
512 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #342 background imageLoading...
Page #342 background image
ENGINEERING MANUAL OF AUTOMATIC CONTROL
CHILLER, BOILER, AND DISTRIBUTION SYSTEM CONTROL APPLICATIONS
332
MULTIPLE BOILER SYSTEMS
GENERAL
Basic boiler connections for a three-zone hot water system
are shown in Figure 47. In this system, two boilers are connected
in parallel. Hot water from the top of the boilers moves to the
air separator which removes any entrapped air from the water.
The expansion tank connected to the separator maintains
pressure on the system. The tank is about half full of water
under normal operating conditions. Air pressure in the tank
keeps the system pressurized and allows the water to expand
and contract as system water temperature varies. Water from
the boiler moves through the separator to the three zone pumps,
each of which is controlled by its own zone thermostat. In some
systems, each zone may have a central pump and a valve. Return
water from the zones returns to the boiler in the return line.
There several variations are possible with this type system but
the process is the same. There is no minimum boiler water flow
limit in this example.
The Dual Boiler Plant Control example following is a dual
boiler plant with high-fire, low-fire controlled boilers, 63°C
minimum entering water temperature required prior to high-
fire, water flow must be maintained when the boiler is enabled,
and a secondary hot water reset schedule of 43°C water at 13°C
OA temperature and 82°C water at –15°C OA temperature. The
concepts adapt well for single or multiple boiler systems.
Fig. 47. Typical Piping for Multiple-Zone
Heating System.
NOTE: The primary/secondary decoupler is sized for the full
secondary flow, and like the chiller plant decoupler,
should be a minimum of 6 pipe diameters in length.
Unlike the chiller decoupler, normal flow may be in
either direction.
EXPANSION
TANK
MAKE-UP
WATER
MANUAL
AIR VENT
PRESSURE
GAUGE
RELIEF
VALVE
PRESSURE
GAUGE
RELIEF
VALVE
BOILER
BOILER
DRAIN
DRAIN
DRAIN
AIR
SEPERATOR
ZONE
HWS
ZONE
HWR
ZONE
HWR
ZONE
HWR
ZONE
HWS
ZONE
HWS
C2905
RETURN
LINE

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AUTOMATIC CONTROL SI Edition and is the answer not in the manual?

Honeywell AUTOMATIC CONTROL SI Edition Specifications

General IconGeneral
BrandHoneywell
ModelAUTOMATIC CONTROL SI Edition
CategoryControl Systems
LanguageEnglish

Related product manuals