INDIVIDUAL ROOM CONTROL APPLICATIONS
ENGINEERING MANUAL OF AUTOMATIC CONTROL
403
Fig. 6. Variable Air Volume Single-Duct With Reheat Air Terminal Unit.
130.35
kPa
WALL MODULE
-1.5
-1.5
-2.0
-1.75
0.543
0.543
0.543
0.543
0.465
0.049
0.236
0.198
72
76
44
38
24
24
24.5
24
24
24
24.5
24
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
0.071LOBBY
ROOM 102
ROOM 103
ROOM 104
0.165
0.260
0.165
MINIMUM MAXIMUM
AIRFLOW SETPOINTS (m
3
/s)
CURRENT
AIRFLOW
(m
3
/s)
DAMPER
PERCENT
OPEN
HEATER
STATUS
HEATING
DEADBAND
TEMPERATURE
COOLING
SETPOINT
M15307
MINIMUM
AIRFLOW
REHEAT
AIRFLOW
MAXIMUM
AIRFLOW
LOWHIGH LOW HIGH
SPACE
HEATING LOAD
HEATING SETPOINT
COOLING SETPOINT
SPACE
COOLING LOAD
DEADBAND
MAXIMUM AIRFLOW
HEATER #2 ON
HEATER #1 ON
HEATER #2 OFF
HEATER #1 OFF
ZERO AIRFLOW
SPACE
PRIMARY
AIR

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell AUTOMATIC CONTROL SI Edition and is the answer not in the manual?

Honeywell AUTOMATIC CONTROL SI Edition Specifications

General IconGeneral
BrandHoneywell
ModelAUTOMATIC CONTROL SI Edition
CategoryControl Systems
LanguageEnglish

Related product manuals