R500
April 2017
Series 8 C300 Controller User's Guide
Honeywell
89
5. C300 Configuration Form Reference
5.1. C300 Controller Block
Plain Text
Parameter Name
User
Configurable
Notes
Synchronization
State
RDNSYNCSTATE
No
Shows C300 Controller's
current synchronization
state.
Battery State
BATTERYNOTOK
No
Indicates if battery voltage
is within 'good' range.
The values displayed by
the BATTERYNOTOK
parameter depends on the
following:
ï‚·
Power supply
ï‚·
Battery backup
ï‚·
Disable Battery Alarm
and Soft Fails field in
the Main tab.
Refer to the Battery State
Values for more
information.
Soft Failures Present
(See Soft Failures
Tab for details)
SOFTFAIL
No
Indicates if Soft Failures
are currently active.
Redundancy Configuration
Module is redundant
MODISREDUN
Project only
Controller is part of
redundant pair
Secondary Tag
Name
SECMODNAME
Project only
System assigned name
based on tag name with
sec suffix for secondary
block.
Advanced Configuration
Alarming Enabled
ALMENBSTATE
Yes
Allows user to set the
alarm reporting function
used when an alarm
condition is detected by
the function block.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell C300 and is the answer not in the manual?

Honeywell C300 Specifications

General IconGeneral
Memory512 MB RAM, 512 MB Flash
TypeProcess Controller
Communication PortsEthernet, Serial
Power Supply24V DC
InputsAnalog and Digital
OutputsAnalog and Digital
CommunicationEthernet, Serial, HART
RedundancySupported (Hot Standby)

Related product manuals