Galaxy 2 Series Installation Manual
2 = Never Unset
The keypad can never unset the system. Unsetting can only be performed by a keyfob, proximity tag or
card.
NOTE: If the panel becomes locked by accidental selection of this option, the panel can be force
unset by the following procedure:
(a) Remove all power from the system.
(b) Open the panel lid tamper.
(c) Re-apply power.
The system will power up unset in a tamper condition.
4. Restart time
This option has two settings:
0 = No (default)
1 = If 1
st
Zn Rpt.
When this option is set to 1 (If 1
st
Zn Rpt.), the confirm timer will be restarted whenever the first to alarm zone
is opened again within the confirm time window. When set to 0 (No), the confirm timer will continue running as
before and will not restart.
5. Reduced Resets
This option allows users to reset the system if there has not been a confirmed alarm signalled.There are two
settings:
0 = Off
This setting makes any alarm follow the reset level in parameter 51.7.
1 = On Unconfirmed (default)
This setting allows the user to reset an unconfirmed alarm, even if parameter 51.7 is set to require a
remote reset.
6. Re-arm mode
This option dictates at what point the re-arm occurs when activated zones are being by-passed and signalled
to the monitoring station. There are two settings:
0 = On Confirm (default)
By-passed zones will send a by-pass signal at the end of the confirm time window.
1 = On Bell Timeout
By-passed zones will send a by-pass signal at the end of the bell time.
7. Entry T/O Confirm
This option determines whether an Entry Timeout alarm will contribute to a confirmed alarm. There are two
settings:
0 = No (default)
1 = Yes
When set to 1 (Yes), a timeout alarm will contribute to a confirmed alarm. When set to 0 (No), a timeout
alarm will only cause an unconfirmed alarm. It will not be counted as either the first or second contribution
to a confirmed alarm.
This must be set to 0, for DD243:2002 compliance.
51 - Parameters (cont’d)

Table of Contents

Other manuals for Honeywell Galaxy 2 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell Galaxy 2 Series and is the answer not in the manual?

Honeywell Galaxy 2 Series Specifications

General IconGeneral
BrandHoneywell
ModelGalaxy 2 Series
CategorySecurity System
LanguageEnglish

Related product manuals