89
Galaxy 2 Series Installation Manual
03 = Fire Delay
This parameter determines the delay between the activation of a fire alarm and the signalling to an ARC. The
Fire Delay is programmable within the range 00-60 seconds. The default is 00 seconds.
04 = Power Delay
This parameter determines the delay between the activation of AC Fail outputs following a mains failure to
allow the power to return before signalling the fault. The Power Delay is programmable within the range
00-60 minutes. The default is 60 minutes.
05 = Part Intruder
This parameter determines under which set conditions the panel communicates following Alarm, Abort, Veri-
fied Alarm and Tamper. There are four sub-options:
0. Full
1. Full & Part
2. Full & Night
3. All (Full, Part and Night) (Default)
This parameter does not affect any other signals. Communication of Set/Unset is only sent for Full Set condi-
tions.
06 = Omit Sig.
This parameter has two options:
0. Force Omit (default)
When set to 0 this option only signals automatic force omits.
1. All Zn Omit
When set to 1 this option signals all omits to the ARC including manual omits.
07 = CS Handshake
This parameter signals handshake tones from the ARC and has three options:
0. UK (default)
1. Belgian
2. Paris
08 = Pre-Dial Flash
This parameter flashes the line to clear it before dialling the ARC and has two options:
0 = No
1 = Yes
09 = STU Return
This parameter determines the return path signalling function of the STU header and has two options:
0 = Off
1 = Intruder Restore
When set to 1, intruder alarms are reset.
56 - Comms (cont’d)