12.2.86 SGx TI (SEGMENT DURATION - x = Segment Number 1 THROUGH 12)
This prompt is part of the Setpoint Ramp/Program Set up group.
A soak segment is a combination of soak setpoint (see SGx SP) and a soak duration.
This is the Soak Setpoint Duration (Time) of Segment x.
.Range of Setting: 0-99 hrs:59 min
12.2.87 SDMODE (SHED MODE)
This prompt is part of the Communications Set up group.
SHED CONTROLLER MODE AND OUTPUT LEVEL—Determines the mode of local
control you want when the controller is shed from the communications link.
Selections Definitions
LAST
SAME MODE AND OUTPUT—The controller will return to the same mode
(manual or automatic) at the same output level that it had before shed.
Man_
MANUAL MODE, SAME OUTPUT—The controller will return to manual
mode at the same output level that it had before shed.
FSAF
MANUAL MODE, FAILSAFE OUTPUT—The controller will return to
manual mode at the output value selected at Control prompt FAILSAFE.
AUTO
AUTOMATIC MODE, LAST SP—The controller will return to the automatic
mode and the last setpoint used before shed
.
12.2.88 SHD_SP (SHED SETPOINT RECALL)
This prompt is part of the Communications Set up group.
The setpoint to be used after Shed is recalled.
Selections Definitions
LSP
Controller will use last local or remote setpoint used.
CSP
When in “slave” mode, the controller will store the last host computer setpoint
and use it at the Local setpoint. When in “monitor” mode, the controller will
shed to the last UDC Local or Remote setpoint used, and the LSP is
unchanged
.
12.2.89 SHDTIM (SHED TIME)
This prompt is part of the Communications Set up group.
The number that represents how many sample periods there will be before the controller
sheds from communications. Each period equals 1/3 seconds; 0 equals No shed.
Range of Setting: 0 to 255 Sample Periods