12.2.83 SECUR (SECURITY CODE)
This prompt is part of the Tuning Set up group.
SECURITY CODE—The level of keyboard lockout may be changed in the Set Up
mode. Knowledge of a “Security code” may be required to change from one level to
another. Select this number here, copy it, and keep it in a secure location.
Entering “0” disables the security code feature.
NOTE: The Security Code is for keyboard entry only and is not available via
communications.
Can only be changed if LOCK selection is NONE.
.Range of Setting: 0 to 4095 (Default = 1000)
12.2.84 SGx RP (SEGMENT RAMP - x = Segment Number 1 THROUGH 12)
This prompt is part of the Setpoint Ramp/Program Set up group.
A ramp segment is the time it takes to change the setpoint to the next setpoint value in the
program.
•Ramps are odd number segments. Segment #1 will be the initial ramp time.
ATTENTION
The selection of time or rate is made at prompt “RP UNIT”.
• Range of Setting:
TIME - Hours:Minutes Range = 0-99 hrs:59 min or
EU-M - Degrees/Minute Range = 0 to 999
EU-H - Degrees/Hour Range = 0 to 999
12.2.85 SGx SP (SEGMENT SETPOINT - x = Segment Number 1 THROUGH 12)
This prompt is part of the Setpoint Ramp/Program Set up group.
A soak segment is a combination of soak setpoint (value) and a soak duration
(see SGx TI).
This is Segment x Soak Setpoint Value
.Range of Setting: within the setpoint limits