● All smart cooling products in a teamwork group must be of the same model.
● Do not directly connect the rst and the last smart cooling products to form a
ring network.
Figure 3-46 Teamwork networking
● The number (n) of smart cooling products in this gure should be less than or equal to
32.
● The teamwork cable between two adjacent smart cooling products must not exceed 10
m in a network.
Teamwork Networking and EMS Monitoring
If both teamwork networking and ESM monitoring are required, the smart cooling
product requires a Y-split cable for collecting and transferring information. Figure
3-47 shows a Y-split cable. Figure 3-48
denes the pins of a Y-split cable. Figure
3-49 shows the Y-split cable connection for teamwork control.
Figure 3-47 Y-split cable
Figure 3-48 Pin denition of a Y-split cable
NetCol5000-A(025, 035) In-row Air Cooled Smart
Cooling Product
User Manual (600 mm Width) 3 Installation Guide
Issue 17 (2020-10-22) Copyright © Huawei Technologies Co., Ltd. 76