Appendix D. SAS expansion enclosure requirements
Before you install a Storwize V7000 2076-12F , 2076-24F , or 2076-92F SAS expansion enclosure, your
physical environment must meet certain requirements. This includes verifying that adequate space is
available and that requirements for power and environmental conditions are met.
Power requirements for each power supply (two per enclosure)
Ensure that your environment meets the following power requirements.
To aid in power and cooling requirements planning, Table 32 on page 157 lists the rating of each power
supply unit (PSU) by enclosure.
The power that is used by the system depends on several factors, including the number of enclosures and
drives in the system and the ambient temperature.
Table 32. Power speciîłcations per power supply
Model and type PSU
Input power
requirements
Maximum input
current
Maximum
power output
Caloric value
(BTU/hr)
 
 
  2076-12F or 
2076-24F
 
 
 
 
 
 
764 W (2)
100 V to 240 V
single phase AC
at a frequency
of 50 Hz to 60
Hz
10A for 100V
6A for 240V
764W 2607
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 2076-92F
2400 W (2)
AC 200-240 
V~ , 
(nominal; +/- 
10% tolerant)
50/60 Hz
(nominal; 
47-63 Hz 
tolerant)
12 A (x2 - per
inlet
redundancy)
Requires an IEC
C20 appliance
coupler
(16-20A branch
circuit or C19
power socket
PDU)
2400W 8189
Note: One or more C19 power distribution units (PDU) are needed in the rack to connect power to
2076-92F power supplies.
Š
 Copyright IBM Corp. 2018 157