Goodrive200 inverters Function codes
116
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
P10.04
Multi-step
speed 1
running direction of simple PLC. The negative
value means reverse rotation.
Multi-step speeds are in the range of --f
max
~f
max
and it can be set continuously.
Goodrive200 series inverters can set 16 steps
speed, selected by the combination of multi-step
terminals 1~4, corresponding to the speed 0 to
speed 15.
When S1=S2=S3=S4=OFF, the frequency input
manner is selected via code P00.06 or P00.07.
When all S1=S2=S3=S4 terminals aren’t off, it
runs at multi-step which takes precedence of
keypad, analog value, high-speed pulse, PLC,
communication frequency input. Select at most
0.0%
P10.05
The
running
time of
step 1
0.0s
P10.06
Multi-step
speed 2
0.0%
P10.07
The
running
time of
step 2
0.0s
P10.08
Multi-step
speed 3
0.0%
P10.09
The
running
time of
step 3
0.0s
P10.10
Multi-step
speed 4
0.0%
P10.11
The
running
time of
step 4
0.0s
P10.12
Multi-step
speed 5
0.0%
P10.13
The
running
time of
step 5
0.0s
P10.14
Multi-step 0.0%