Multi-step speeds are in the range of --f
max
~f
max
and it can be set continuously.
Goodrive200 series inverters can set 16 steps
speed, selected by the combination of multi-step
terminals 1~4, corresponding to the speed 0 to
speed 15.
When S1=S2=S3=S4=OFF, the frequency input
manner is selected via code P00.06 or P00.07.
When all S1=S2=S3=S4 terminals aren’t off, it
runs at multi-step which takes precedence of
keypad, analog value, high-speed pulse, PLC,
communication frequency input. Select at most
0.0% ○
P10.05