CHAPTER 6
Rack and Cabinet Requirements
Cabinet Requirements for ACX1000 and ACX1100 Routers on page 51
Rack Requirements for ACX1000 and ACX1100 Routers on page 52
Cabinet Requirements for ACX1000 and ACX1100 Routers
You can mount the router in a cabinet that contains a 19-in. (48.3 cm) rack.
Cabinet requirements consist of:
Cabinet size
Clearance requirements
Cabinet airflow requirements
Table 19 on page 51 provides the cabinet requirements and specifications for the router.
Table 19: Cabinet Requirements and Specifications for the ACX1000 and ACX1100 Router
GuidelinesCabinet Requirement
You can mount the router in a cabinet that contains a 19-in.
(48.3 cm) rack as defined in Cabinets, Racks, Panels, and
Associated Equipment (document number EIA-310–D)
published by the Electronics Industry Association
(http://www.eia.org).
NOTE: The cabinet must meet the strength requirements
to support the weight of the router.
The minimum cabinet size must be able to accommodate
the maximum external dimensions of the router.
Cabinet size
The outer edges of the mounting brackets extend the width
of the chassis to 19 in. (48.3 cm).
The minimum total clearance inside the cabinet is 30 in.
(76.2 cm) between the inside of the front door and the inside
of the rear door.
Cabinet clearance