Commissioning
Commissioning via DIP switch/potentiometer
DIP switch / potentiometer assignment 1
6
l
134
EDS84DG752 EN 7.0
Settings with P2
(Lenze setting bold)
Use P2 to write different preset setpoints to C00039/1 and C00039/2.
P2 Setting
Description 0 1 2 3 4 5 6 7 8 9
Write preset setpoint1 to C00039/1 [%] 5 10 15 20 25 30 35 40 45 50
Write preset setpoint2 to C00039/2 [%] 10 20 30 40 50 60 70 80 90 100
Settings with P3
(Lenze setting bold)
Use P3 to write different acceleration/deceleration times to C00012/C00013 including
different deceleration times for quick stop to C00105.
P3 Setting
Description 0 1 2 3 4 5 6 7 8 9
Write acceleration/deceleration time to
C00012/C00013
[s] 0.1 0.5 0.7 1 1.5 2 5 10 30 60
Write deceleration time for quick stop to C00105 [s] 0.1 0.2 0.5 0.7 1 1.5 2 5 10 30
Settings with P1
(Lenze setting bold)
Use P1 to write a preset speed setpoint to C00039/3. Depending on the switch position of
DIP1/7, C00039/3 is written to once or permanently at mains connection.
Remove cap in order to be able to set the P1 potentiometer.
ƒ Screw cap on again after the setting process, in order to ensure the degree of
protection of the inverter.
P1 Setting
Description 0 ... 9
Write preset setpoint3 to C00039/3 [%] 0 ... 100