Technical data
Power terminals
8400 motec 4...7.5kW
4
l
55
EDS84DG752 EN 7.0
4.6.2 8400 motec 4...7.5kW
X1/X2
E84DG124
Mains
Terminal data
Name Power Conductor cross−section
[mm
2
]
[AWG]
Tightening torque
[Nm]
[lb−in]
!
X1
L1, L2, L3
4.0...7.5kW
1 ... 16
18 ... 6
1.4
12
PZ 2
5.5 x 10
2 x 1 ... 2 x 6
1)
18 ... 6
+
PE 4.0...7.5kW 1 ... 16
18 ... 6
1.7
15
8 x 1.2
1)
For looping−through connections (daisy chain) => two conductors with TWIN wire end ferrule
) Note!
Terminal X1 is not pluggable.
Features
Name Description Rated value
X1
L1, L2, L3
Mains phases See rated data