EasyManua.ls Logo

Lenze 8400 motec - 5 Installation; Important Notes

Lenze 8400 motec
172 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation
Important notes
5
l
70
EDS84DG752 EN 7.0
5 Installation
5.1 Important notes
{ Danger!
Dangerous electrical voltage
All power terminals remain live for up to three minutes after mains
disconnection.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Switch off the power supply and wait for at least three minutes before
working on the power terminals.
ƒ Make sure that all power terminals are deenergised.
{ Danger!
Hazardous electrical voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
ƒ Death or severe injuries when touching the device in the event of an error.
Protective measures:
Implement the measures required in EN 61800−5−1. Especially:
ƒ Fixed installation
Implement PE connection in compliance with standards.
Connect PE conductor twice or PE conductor cross−section ³ 10 mm
2
.
ƒ Connection with a connector for industrial applications according to
IEC 60309 (CEE):
PE conductor cross−section ³ 2.5 mm
2
as part of a multi−core supply cable.
Provide for suitable strain relief.
{ Danger!
Hazardous electrical voltage
Terminals T1, T2 are on DC−bus voltage potential.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Before working on the terminals, disconnect mains and wait for at least
3 minutes.
ƒ Check whether the terminals are deenergised.