Commissioning
Commissioning via DIP switch/potentiometer
DIP switch / potentiometer assignment 0
6
l
128
EDS84DG752 EN 7.0
6.3.1 DIP switch / potentiometer assignment 0
Settings with DIP1
(Lenze setting bold)
DIP1 Switch
Description 1 2 3 4 5 6 7 8
DIP1, DIP2, P1, P2,
and P3 active
Active
ON
Inactive
OFF
Direction of
rotation
left
ON
right
OFF
Control
square−law
ON
linear
OFF
Flying restart
circuit
active
ON
inactive
OFF
Reserved OFF OFF OFF
Device status
Drive Ready: NO/COM= Closed
ON
Drive Fail: DO1=HIGH
Device status
Drive Ready: DO1=HIGH
OFF
Drive Fail: NO/COM= Closed
Settings with DIP2
(Lenze setting bold)
DIP2 Switch
Description 1 2 3 4 5 6 7 8
Rated motor
frequency /
reference speed
50 Hz * / 1500rpm
OFF
OFF
60 Hz * / 1800rpm
ON OFF
87 Hz - / 2610rpm
OFF ON
120Hz * / 3600rpm
ON ON
Analog input mode
0 ... 10 V
OFF OFF
0 ... 20 mA
ON OFF
4 ... 20 mA
OFF ON
Not permissible ON ON
Control mode −
technology
application
9 (Local mode)
OFF OFF OFF
10 (terminals 0)
ON OFF OFF
12 (terminals 2)
OFF ON OFF
14 (terminals 11)
ON ON OFF
16 (terminals 16)
OFF OFF ON
Reserved
ON OFF ON
Reserved
OFF ON ON
40 (MCI)
ON ON ON
Reserved OFF