Technical data
Power terminals
8400 motec 4...7.5kW
4
l
56
EDS84DG752 EN 7.0
Motor
Terminal data
Name Power Conductor cross−section
[mm
2
]
[AWG]
Tightening torque
[Nm]
[lb−in]
!
X2
U, V, W
4.0...7.5kW 1 ... 6
18 ... 8
0.8
7
PH 1
3.5 x 0.6
+
PE 4.0...7.5kW 1 ... 16
18 ... 6
1.7
15
8 x 1.2
Features
Name Description Rated value
X2
U, V, W
Motor phases See rated data
Motor temperature monitoring
{ Danger!
Hazardous electrical voltage
Terminals T1, T2 are on DC−bus voltage potential.
Possible consequences:
ƒ Death or severe injuries when touching the power terminals.
Protective measures:
ƒ Before working on the terminals, disconnect mains and wait for at least
3 minutes.
ƒ Check whether the terminals are deenergised.
Terminal data
Name Power Conductor cross−section
[mm
2
]
[AWG]
Tightening torque
[Nm]
[lb−in]
!
X2
T1, T2
0.37...1.5kW
1.5
16
0.5
4.4
3.5 x 0.6
2.2...3.0kW
1 ... 6
18 ... 8
0.8
7.0
3.5 x 0.6
Features
Name Description Rated value
X2
T1, T2
Motor temperature monitoring See rated data
Danger! Hazardous electrical voltage.
l T1 and T2 have DC−bus voltage potential .