Technical data
Rated data
Operation at rated mains voltage 400 V
4
l
38
EDS84DG752 EN 7.0
Fuses and cable cross−sections
ƒ Point−to−point connection − direct wiring of the mains voltage − typical fusing
Operation
Type Installation according to EN 60204−1
1)
Installation according
to UL
2)
FI
3)
L1, L2, L3 − laying system L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E84DGDVB3714 C 16 16 2.5 15 12 ³ 30
E84DGDVB5514 C 16 16 2.5 15 12 ³ 30
E84DGDVB7514 C 16 16 2.5 15 12 ³ 30
E84DGDVB1124 C 16 16 2.5 15 12 ³ 30
E84DGDVB1524 C 16 16 2.5 15 12 ³ 30
E84DGDVB2224 C 16 16 2.5 15 12 ³ 30
E84DGDVB3024 C 16 16 2.5 15 12 ³ 30
E84DGDVB4024 C20 20 4.0 20 12 ³ 30
E84DGDVB5524 C20 20 4.0 20 12 ³ 30
E84DGDVB7524 C 20 20 4.0 20 12 ³ 30
ƒ Multiple connection − loop−through connection of the mains voltage − maximum
fusing
Operation
Type Installation according to EN 60204−1
1)
Installation according
to UL
2)
FI
3)
L1, L2, L3 − laying system L1, L2, L3
B2 C F
[A] [A] [mm
2
] [mm
2
] [mm
2
] [A] [AWG] [mA]
E84DGDVB3714 C 32 32 6.0 15 12 ³ 30
E84DGDVB5514 C 32 32 6.0 15 12 ³ 30
E84DGDVB7514 C 32 32 6.0 15 12 ³ 30
E84DGDVB1124 C 32 32 6.0 15 12 ³ 30
E84DGDVB1524 C 32 32 6.0 15 12 ³ 30
E84DGDVB2224 C 32 32 6.0 25 10 ³ 30
E84DGDVB3024 C 32 32 6.0 25 10 ³ 30
E84DGDVB4024 C 50 50 16.0 50 6 ³ 30
E84DGDVB5524 C 50 50 16.0 50 6 ³ 30
E84DGDVB7524 C 50 50 16.0 50 6 ³ 30
1)
The data are recommendations. Other designs/laying systems can be implemented (e.g. in accordance with VDE
0298−4). The cable cross−sections apply under the following conditions: Use of PVC−insulated copper cables,
conductor temperature < 70 °C, ambient temperature < 45°C, no bundling of cables or cores, three loaded cores.
2)
Only use UL−approved cables, fuses and fuse holders.
UL fuse: voltage £ 500 V, tripping characteristic for instance "CC". The cable cross−sections apply under the following
conditions: conductor temperature < 75 °C, ambient temperature < 45°C.
3)
Universal−current sensitive earth−leakage circuit breaker, short−time delayed
Circuit breaker
Fuse of gG/gL utilisation category or semiconductor fuses of gRL utilisation category
Fuse
Observe national and regional regulations