Technical data
Rated data
Operation with increased power at a 400 V mains
4
l
40
EDS84DG752 EN 7.0
Output currents [A] at switching frequency
2 kHz 4 kHz 8 kHz 16 kHz
Type I
arated2
I
aM2
I
arated4
I
aM4
I
arated8
I
aM8
I
arated16
I
aM16
E84DGDVB3714 − − 1.6 2.6 − − − −
E84DGDVB5514 − − 2.2 3.6 − − − −
E84DGDVB7514 − − 3.0 4.8 − − − −
E84DGDVB1124 − − 3.8 6.4 − − − −
E84DGDVB1524
1)
− − 4.8 7.8 − − − −
E84DGDVB2224 − − 7.0 11.2 − − − −
E84DGDVB3024
1)
− − 8.7 14.6 − − − −
E84DGDVB4024 − − 11.6 19.0 − − − −
E84DGDVB5524 − − 15.6 26.0 − − − −
E84DGDVB7524
2)
− − 19.8 33.0 − − − −
1) Operation with increased rated power for motor mounting only.
2) Motor connection with plug (Q8) not permissible.
I
aNx
Rated value of continuous output current
I
aMx
Maximum output current (overload current)
l Periodic load change of 3 s with I
aMx
and recovery time of 12 s according to
the tables under chapter ^ 4.4
Fuses and cable cross−sections
The data/recommendations for operation on a rated mains voltage 400 V can be applied.