5 SYSTEM CONFIGURATION
5.4 Structure of CC-Link IE TSN Class B/A Devices (CC-Link IE TSN Protocol Version 1.0 Only) and Ethernet Devices
• When the communication speed of the master station is 1Gbps, a connection cannot be established if the total cyclic data
size of all device stations on the 100Mbps device side exceeds 2K bytes. This includes the devices with a communication
speed of 100Mbps that form a boundary between the communication speed of 1Gbps and 100Mbps.
No.0: Master station
No.1, No.10: Local station
No.2, No.3, No.4, No.5, No.6, No.7, No.8, No.9: Remote station
Set the total cyclic data size within 2K bytes.
No.1
Class B (1Gbps)
No.4
Class B (1Gbps)
No.3
Class B (1Gbps)
No.8
Class B (100Mbps)
No.7
Class B (100Mbps)
No.9
Class A (100Mbps)
No.0
Class B (1Gbps)
No.5
Class A
(100Mbps)
No.6
Class A
(100Mbps)
No.5
Class A
(100Mbps)
Ò
Ò
No.2
Class B (1Gbps)
Industrial switch
(for CC-Link IE TSN
Class B)
Industrial switch
(for CC-Link IE TSN
Class B)