5 SYSTEM CONFIGURATION
5.5 Connection Examples
Structure of CC-Link IE TSN Class B/A devices only
Connection of inverters (Only the master station is CC-Link IE TSN Class B.)
If an industrial switch is used to configure a system (master station: 1Gbps)
The following figure shows connection of master/local module (1Gbps) + inverters. (Only the master station is CC-Link IE TSN
Class B.)
When all the device stations are CC-Link IE TSN Class A, they can be connected up to the maximum
number of connectable stations specified in the CC-Link IE TSN performance specifications.
If the firmware version is "1.002" or earlier, use an industrial switch (for CC-Link IE TSN Class A) that
supports the communication speed of 1Gbps/100Mbps to convert the communication speed.
If the firmware version is "1.010" or later, use an industrial switch (for CC-Link IE TSN Class B) or industrial
switch (for CC-Link IE TSN Class A) that supports the communication speed of 1Gbps/100Mbps to convert
the communication speed to 100Mbps. When using an industrial switch (for CC-Link IE TSN Class B), set
"TSN HUB Setting" to "Use TSN HUB".
Connection after the industrial switch (for CC-Link IE TSN Class B) or industrial switch (for CC-Link IE TSN
Class A) can be a line topology, star topology, or coexistence of line and star topologies.
Set "Connection Device Information" of the master station parameters to "Mixture of CC-Link IE TSN Class
B/A or CC-Link IE TSN Class A Only". In "Network Configuration Settings" under "Basic Settings", set
"Communication Period Setting" of the inverters to "Low-Speed".
No.0: FX5-CCLGN-MS (Master station)
No.1, No.2, No.3, No.4, and No.5: Inverter (Remote station)
No.0
Class B (1Gbps)
No.1
Class A (100Mbps)
No.2
Class A (100Mbps)
No.3
Class A (100Mbps)
No.5
Class A (100Mbps)
No.4
Class A (100Mbps)
Industrial switch
(for CC-Link IE TSN Class A)
or
Industrial switch
(for CC-Link IE TSN Class B)