4.4 Ethernet Connection
4.4 Ethernet Connection
This function connects an Ethernet device to a module without interfering with CC-Link IE TSN.
Connection with MELSOFT products
Programming and monitoring of the programmable controller are performed via Ethernet using the engineering tool. This
function enables remote control using long-distance connectivity and high-speed communications via Ethernet.
The following table lists the methods of connecting the FX5-CCLGN-MS to MELSOFT products (such as engineering tool).
: Connection available, : Connection not available
A station with a communication speed different from the communication speed of the station to which the
engineering tool is connected cannot be connected by specifying another station. The online and debug
function of the engineering tool may not be used.
When a MELSOFT product or GOT is connected via the FX5-CCLGN-MS, a connection cannot be
established if another FX5-CCLGN-MS to which the same network number is set is mounted on the CPU
module connected to the FX5-CCLGN-MS.
Connection via a HUB
Settings on the FX5-CCLGN-MS side
For connection by specifying the IP address, set the IP address using "Required Settings". ( Page 131 Station No./IP
Address Setting)
For connection by specifying the network number and station number, set the network number and station number in
"Required Settings".
Neither of connections require "Network Configuration Settings" under "Basic Settings".
Connection method Purpose Availability Reference
MELSOFT
product
Connection via a HUB
(Connection by specifying the IP address)
To connect multiple MELSOFT products Page 48 Connection
via a HUB
Connection via a HUB
(Connection by specifying the network number
and station number)
To connect multiple MELSOFT products