7 PARAMETER SETTINGS
7.1 Setting Parameters
129
7
7 PARAMETER SETTINGS
This chapter describes the parameter settings required for communications between the FX5-CCLGN-MS and other stations.
7.1 Setting Parameters
1. Add the FX5-CCLGN-MS in the engineering tool.
[Navigation window] [Parameter] [Module Information] Right-click [Add New Module]
2. The required settings, basic settings, and application settings are included in the parameter settings. Select one of the
settings from the tree on the following window.
[Navigation window] [Parameter] [Module Information] Ta r ge t Mo du l e
3. After setting parameters, click the [Apply] button.
4. Write parameters to the FX5 CPU module using the engineering tool.
[Online] [Write to PLC]
5. The parameters are reflected by resetting the FX5 CPU module or powering off and on the system.
7.2 Required Settings
Set such items as the station type and network number of the FX5-CCLGN-MS.
Station Type
Set the station type of the FX5-CCLGN-MS.
Item Description Reference
Station Type Set the station type of the FX5-CCLGN-MS. Page 129 Station Type
Network No. Set the network number of the FX5-CCLGN-MS. Page 130 Network No.
Parameter Setting Method Set "Basic Settings" and "Application Settings" items using the engineering tool or in
program.
Page 130 Parameter
Setting Method
Station No./IP Address Setting Set the station number or IP address of the FX5-CCLGN-MS. Page 131 Station No./IP
Address Setting
Item Description Setting range
Station Type Select whether to use the FX5-CCLGN-MS as the master station or
local station.
Only one master station can be set in a network.
•Master Station
• Local Station
(Default: Station type set in the "Add New Module"
window.)