6 WIRING
6.1 Power Supply Wiring
125
6
6 WIRING
This chapter describes the wiring methods, wiring products, and wiring precautions when using the FX5-CCLGN-MS.
6.1 Power Supply Wiring
Power connector layout
Power supply wiring
Grounding
Observe the following:
Provide grounding with a ground resistance of 100 or less.
Provide independent grounding when possible.
If independent grounding cannot be provided, provide "shared grounding" as shown below.
Keep the distance between the grounding point and the programmable controller as close as possible to shorten the length
of ground cable.
+
-
(Green)
(Black)
(Red)
Ground resistance of
100 ohms or less
(Grounding resistance:
100: or less)
24VDC
Red
Black Green
Master/local module
Programmable
controller
Another
device
Programmable
controller
Another
device
Programmable
controller
Another
device
Shared grounding
(Good condition)
Common grounding
(Not allowed)
Independent grounding
(Best condition)