5 SYSTEM CONFIGURATION
5.5 Connection Examples
123
5
Structure of CC-Link IE TSN Class B/A devices and Ethernet
devices
Connection of Ethernet devices
The configuration for connecting Ethernet devices to CC-Link IE TSN-compatible devices or industrial switches (for CC-Link
IE TSN Class A) in the configuration is shown below.
The Ethernet devices (1Gbps) can be directly connected to unused ports of the CC-Link IE TSN-compatible
devices without the industrial switch.
The Ethernet devices (100Mbps) can be connected to industrial switches (for CC-Link IE TSN Class A)
installed on the boundary between the CC-Link IE TSN Class B and CC-Link IE TSN Class A device areas.
The Ethernet devices can perform MELSOFT connection and SLMP communications with the master
station. They also can communicate with each other using a protocol that supports each other. For the
maximum number of MELSOFT connection and SLMP communications, refer to the following.
Page 17 Performance Specifications of Ethernet
Since the CC-Link IE TSN-compatible devices have a smaller memory capacity for packet reception
compared to the industrial switches, packets may not reach external devices if the Ethernet devices are
directly connected and high-frequent communications are performed.
Since Ethernet communications use the transient transmission band on CC-Link IE TSN, the throughput of
the Ethernet communications may decrease when the basic communication cycle is extremely short or
when a large number of packets are communicated. This can be solved by correcting the communication
frequency and the number of connected Ethernet devices.
No.0: FX5-CCLGN-MS (master station)
No.1, No.2, and No.3: Remote I/O module (remote station)
No.4, No.5, and No.6:Inverter (remote station)
(1), (2), (3), (4): Ethernet device
CC-Link IE TSN Class B device area
CC-Link IE TSN Class A device area
No.1
Class B (1Gbps)
No.3
Class B (1Gbps)
No.0
Class B (1Gbps)
No.4
Class A (100Mbps)
No.5
Class A (100Mbps)
No.6
Class A (100Mbps)
No.2
Class B (1Gbps)
Ò Ó
(1)
(4)
(3)
(2)
Industrial switch
(for CC-Link IE
TSN Class A)
or
Industrial switch
(for CC-Link IE
TSN Class B)