7 PARAMETER SETTINGS
7.3 Basic Settings
135
7
Network Topology
Select the network topology type according to the actual network configuration.
Setting is not required and can be left as "Line/Star" (default).
Communication Period Setting
Perform basic cycle setting and multiple cycle setting.
Basic cycle setting requires calculation of the communication cycle interval and cyclic transmission time. ( Page 286
Communication cycle intervals)
Multiple cycle setting is used when communication cycles coexist. ( Page 39 Communication cycle coexistence)
When the industrial switch (for CC-Link IE TSN Class B) is used, set the timeslot information from the
setting values in "Basic Period Setting". The timeslot information can be checked with the buffer memory.
( Page 257 Timeslot information)
Set "Communication Period Setting" according to the communication cycle supported by the device
stations.
Item Description Setting range
Basic Period
Setting
Setting in Units of 1s Select whether to set the basic cycle in increments of 1s. Set
Do Not set
(Default: Do Not set)
Communication Period Interval Setting
(Do Not Set it in Units of 1s)
Input a communication cycle interval. 250.00s
•500.00s
1000.00s
2000.00s
4000.00s
8000.00s
(Default: 1000.00s)
Communication Period Interval Setting
(Set it in Units of 1s)
Input a communication cycle interval. 250.00s to 10000.00s (in
increments of 1s)
(Default: 1000.00s)
System Reservation Time Necessary time for the system to guarantee the
communication cycle interval.
•20.00s
•200.00s
(Default: 20.00s)
Cyclic Transmission Time Of communication cycle intervals, set the time to be allocated
to cyclic transmission.
5.00s to 9966.00s (in
increments 1s)
(Default: 500.00s)
Transient Transmission Time The value of "Communication Period Interval Setting" minus
"Cyclic Transmission Time" and "System Reservation Time" is
displayed.
14.00s to 9975.00s (in
increments of 1s)
(Default: 480.00s)
Multiple Cycle
Setting
Normal-Speed Select the "Normal-Speed" cycle for a basic cycle.
Setting is not required and can be left as "4".
(Default: 4)
Low-Speed Select the "Low-Speed" cycle for a basic cycle. 16
32
64
12
8
(Default: 16)