10 TROUBLESHOOTING
10.7 Event List
245
10
10.7 Event List
This section lists the events which occur in CC-Link IE TSN.
The event history is displayed when the [Event History] button in the [Error Information] tab in the "Module Diagnostics"
window of the FX5-CCLGN-MS is clicked. ( Page 198 Error Information)
System
Event
code
Description Cause
00800 Link-down The system was linked down by removing a device (such as an external device).
00907 Divided messages receive timeout error Sufficient data for the data length could not be received.
The remaining part of the divided message could not be received.
00C40 Device station parameter automatic setting:
Interruption
An abnormal response was received from the device station, and device station
parameter automatic setting processing was interrupted. (For details on device station
response codes, refer to the manual for the device station.)
00C41 Device station parameter automatic setting:
Parameter update interruption
An abnormal response was received from the device station, and parameter update
processing for the device station parameter automatic setting was interrupted. (For
details on device station response codes, refer to the manual for the device station.)
00C42 Device station parameter automatic setting: System
error
An error occurred while the device station parameter automatic setting was executing.
00C43 Device station parameter automatic setting:
Transmission timeout
Transmission timed out while communicating with the device station parameter
automatic setting.
00C44 Device station parameter automatic setting: Receive
timeout
The specified period of time expired without receiving while communicating with the
device station parameter automatic setting.
00C46 Device station parameter automatic setting: SLMP
transmission error
An error occurred while transmitting with SLMP for the device station parameter
automatic setting.
00C47 Device station parameter automatic setting: CPU
module access failure
Access to the CPU module failed during device station parameter automatic setting.
00C48 Device station parameter automatic setting: No target
station parameter
The device station parameter file targeted during device station parameter automatic
setting was not stored in the CPU module. Or, the writing destination of the device
station parameter is different from the setting of the memory card parameter.
00C54 Initialization failure A communication error occurred in the initialization processing when control
communications started.
00C70 CANopen initialization failure A communication error occurs in CANopen initialization processing.
00C72 Maximum response time mismatch for the time
managed polling method
A maximum response time mismatch was detected for the time managed polling
method.
Update the engineering tool and the device stations to the latest version.
00C80 Detection of device station that does not support the
CC-Link IE TSN Protocol version 2.0
A device station that does not support the CC-Link IE TSN Protocol version 2.0 was
detected.
00C81 CC-Link IE TSN Class mismatch A mismatch was detected between the parameter of the master station and the CC-Link
IE TSN Class of the device stations.