7 PARAMETER SETTINGS
7.5 "CC-Link IE TSN Configuration" Window
147
7
Procedure for clearing a saved parameter
When returning the saved parameters of a not-required device station to the not-set status, perform the following procedure.
1. If the saved parameters are to be saved, output them in a CSV file using the [Export] button.
2. Delete not-required device stations from the list of stations.
3. Select the same module as the deleted device station in "Module List", and drag it to the list of stations or the network
map.
Conditions for clearing a saved parameter
Saved parameters of a device station can be cleared under the following conditions.
When saved parameters are cleared, execute "Parameter auto-setting" or "Parameter read" in the "Parameter of Device
Station" window and read the parameters of the device station.
Item Description
Target Module Information Information for the selected device stations is displayed.
Method selection Select processing to be executed for selected device stations.
• Parameter auto-setting: Automatically set contents of "Write Value/Setting Value" to the device
station. ( Page 62 Device station parameter automatic setting)
• Parameter read: Read parameters from the selected device station.
• Parameter write: Write parameters to the selected device station.
Parameter
Information
[Clear All "Read Value"] button Click to clear all setting details that were read using "Parameter read".
[Clear All "Write Value/Setting Value"]
button
Click to clear all setting details that are written using "Parameter write".
Processing option When there are options for processing selected by "Method Selection", setting items are
displayed.
[Import] button Read contents of parameter processing created in a CSV file.
[Export] button Output contents of parameter processing set in this window to a CSV file.
Item Operation Description
"CC-Link IE TSN
Configuration" window
Open the "CC-Link IE TSN Configuration" window. When there is not a device station with the station number that
matches saved parameters in the "CC-Link IE TSN Configuration"
window, saved parameters of the relevant device station are
skipped.
Skipped parameters of the device station are cleared.
Reflect setting and close the window. Saved parameters of a device station that is not in the actual
system configuration are cleared.
Execute detection of connected/disconnected devices. All saved parameters are cleared.
Change the function version in the "Properties" window. When the "Properties" window is closed, saved parameters are
cleared.
"Parameter of Device
Station" window
Open the "Parameter of Device Station" window. Saved parameters that mismatch the relevant device station are
skipped.
Clicking the [Close with Reflecting the Setting] button in the above
state clears the skipped saved parameters.
Module Parameter Manually delete "Network Configuration Settings" to apply. Parameters of "Network Configuration Settings" return to default.
Change the "Setting Method of Basic/Application Settings"
under "Parameter Setting Method" in "Required Settings"
from "Parameter Editor" to "Program".
Change "Station Type" or set parameters that do not exist.
System Parameter Divert system parameters from another project. Parameters of the device station are not diverted.
Module Configuration Delete a module and check. Parameters are deleted together with the module.
Navigation window Delete a module.
Read from PLC Read module parameters that have a different network
configuration and the same Intelligent module No.
Parameters are overwritten.
Navigation window Import the data of a simple motion module to take network
settings.
MELSOFT Navigator Reflect the parameter. Saved parameters are cleared.