10 TROUBLESHOOTING
10.4 Troubleshooting by Symptom
The connection device
information of the master
station is set to "Mixture of
CC-Link IE TSN Class B/A or
CC-Link IE TSN Class A
Only".
For firmware version "1.010" or later
Is the event code 00C81 registered in the event history?
Change "CC-Link IE TSN Class" under "Network
Configuration Settings" or "CC-Link IE TSN Class" on the
device station side so that the "CC-Link IE TSN Class" for
each station match.
When the device stations to be used operate with the CC-Link
IE TSN Protocol version 2.0, is a master station that does not
support the CC-Link IE TSN Protocol version 2.0 used?
Update the firmware of the master station to a version
supporting the CC-Link IE TSN Protocol version 2.0.
Replace the master station with a master station supporting
the CC-Link IE TSN Protocol version 2.0.
For devices supporting the CC-Link IE TSN Protocol version
2.0
Is the event code 00C80 registered in the event history?
Take one of the following actions.
Check 'CC-Link IE TSN Protocol version 2.0 support status
for each station' (SW01A0 to SW01A7) and update the
firmware of all the device stations to a version that supports
the CC-Link IE TSN Protocol version 2.0. Alternatively,
replace with device stations that support protocol version
2.0.
For firmware version "1.010" or later, set the operating
protocol to the CC-Link IE TSN Protocol version 1.0 fixed.
Page 260 Protocol information
Power on the device stations and devices in the
communication path, and then power on the master station.
For devices supporting the
CC-Link IE TSN Protocol
version 2.0
Is 'Protocol operating status'
(Un\G44320) set to "2" (A
device is operating with the
CC-Link IE TSN Protocol
version 2.0)?
Is 'CC-Link IE TSN Protocol
version 2.0 support status for
each station' (SW01A0 to
SW01A7) set to "0: Not
supported"?
Take one of the following actions.
Check 'CC-Link IE TSN Protocol version 2.0 support status
for each station' (SW01A0 to SW01A7) and update the
firmware of all the device stations to a version that supports
the CC-Link IE TSN Protocol version 2.0. Alternatively,
replace with device stations that support protocol version
2.0.
For firmware version "1.010" or later, set the operating
protocol to the CC-Link IE TSN Protocol version 1.0 fixed.
Page 260 Protocol information
Power on the device stations and devices in the
communication path, and then power on the master station.
For devices supporting the
CC-Link IE TSN Protocol
version 2.0
Is 'Protocol operating status'
(Un\G44320) set to "1" (A
device is operating with the
CC-Link IE TSN Protocol
version 1.0)?
Is 'CC-Link IE TSN Protocol
version 2.0 support status for
each station' (SW01A0 to
SW01A7) set to "0: Not
supported"?
Update the firmware of all the device stations to a version
supporting the CC-Link IE TSN Protocol version 2.0.
Alternatively, replace with device stations that support
protocol version 2.0.
Are nine or more CC-Link IE
TSN Class B devices and
industrial switches connected
in total to each port of the
master station in the
transmission path from the
master station to the CC-Link
IE TSN Class B device of the
end?
Check the connected devices and reduce the number of CC-
Link IE TSN Class B devices and industrial switches to eight
or less in total for each port of the master station in the
transmission path from the master station to the CC-Link IE
TSN Class B device of the end.
Does the cyclic data size
exceed 2K bytes in total for
CC-Link IE TSN Class A
devices connected to a CC-
Link IE TSN Class B device
other than the master
station? (Including when an
industrial switch is used to
connect to a CC-Link IE TSN
Class B device)
Use an industrial switch (for CC-Link IE TSN Class B) to
connect to CC-Link IE TSN Class B devices. (When an
industrial switch is used to establish a connection, change
the industrial switch (for CC-Link IE TSN Class A) to an
industrial switch (for CC-Link IE TSN Class B).)
Restrict the number of connected stations so that the cyclic
data size of the CC-Link IE TSN Class A devices does not
exceed 2K bytes in total.
Connect the CC-Link IE TSN Class A devices to the master
station.
For devices supporting the CC-Link IE TSN Protocol version
2.0
Do the system configuration of mixture of CC-Link IE TSN
Class B/A and "TSN HUB Setting" in "Connection Device
Information" under "Basic Settings" differ?
For details, refer to the following.
P
age 220 A CC-Link IE TSN Class A device does not
perform data link.
Check item Action