10 TROUBLESHOOTING
10.5 List of Error Codes
225
10
3010H The value set in "Communication Period Interval
Setting" in "Communication Period Setting" under
"Basic Settings" of the master station is smaller
than the communication cycle interval calculated
by the number of stations and points of device
stations that was set in "Network Configuration
Settings" under "Basic Settings".
Set the value of "Communication Period Interval Setting" as a value
equal to or larger than the value in the detailed information displayed
in "Module Diagnostics" using "Communication Period Setting" under
"Basic Settings" of the master station.
If the detailed information value exceeds the upper limit of
"Communication Period Interval Setting" that can be set in the master
station, reduce the number of modules connected to the master
station and the number of link devices assigned to each module in
"Network Configuration Settings", so that the upper limit of
"Communication Period Interval Setting" is not exceeded.

Communication
Period Interval
Information
Communication
cycle interval
(calculation value:
s)
3011H The value set in "Cyclic transmission time" in
"Communication Period Setting" under "Basic
Settings" of the master station is smaller than the
cyclic transmission time calculated by the number
of stations and points of device stations set in
"Network Configuration Settings" under "Basic
Settings".
Set the value of "Cyclic Transmission Time" as a value equal to or
larger than the value in the detailed information displayed in "Module
Diagnostics" using "Communication Period Setting" under "Basic
Settings" of the master station.
If the detailed information value exceeds the upper limit of "Cyclic
Transmission Time" that can be set in the master station, reduce the
number of modules connected to the master station and the number
of link devices assigned to each module in "Network Configuration
Settings", so that the upper limit of "Cyclic Transmission Time" is not
exceeded.

Communication
Period Interval
Information
Cyclic
Transmission Time
(Calculation value:
s)
3012H System error Please consult your local Mitsubishi representative.
3013H The value set in "Transient Transmission Time" in
"Communication Period Setting" under "Basic
Settings" of the master station is smaller than the
transient transmission time calculated using the
number of device stations and the points of device
stations set in "Network Configuration Settings"
under "Basic Settings".
Set "Communication Period Interval Setting" and "Cyclic
Transmission Time" so that the value of "Transient Transmission
Time" in "Communication Period Setting" under "Basic Settings" of
the master station is equal to or larger than the value shown in the
detailed information displayed in "Module Diagnostics".

Communication
Period Interval
Information
Transient
Transmission Time
(Calculation value:
s)
3014H When "Communication Mode" under "Application
Settings" of the master station is set to "Multicast",
in the "Network Configuration Settings" of the
"Basic Settings", "Communication Period Setting"
of the local station is set to "Normal-Speed" or
"Low-Speed".
Set "Communication Mode" in "Application Settings" of the master
station to "Unicast".
In "Network Configuration Settings" under "Basic Settings" of the
master station, set "Communication Period Setting" of the local
station to "Basic Period".
Parameter
information
Parameter type
Intelligent module
No.
Parameter No.
Target station
information
Station Number
IP address
3015H The value set in "Communication Period Interval
Setting" in "Communication Period Setting" under
"Basic Settings" of the master station is smaller
than the communication cycle interval calculated
by the number of stations and points of device
stations that was set in "Network Configuration
Settings" under "Basic Settings".
Set the value of "Communication Period Interval Setting" as a value
equal to or larger than the value of "Communication cycle interval
(Calculation value)" (SW0072) of a local station using
"Communication Period Setting" under "Basic Settings" of the master
station. ( Page 286 Communication cycle intervals)
If the same error occurs again even after taking the above, please
consult your local Mitsubishi representative.
3016H System error Please consult your local Mitsubishi representative.
3
017H The value set in "Cyclic transmission time" in
"Communication Period Setting" under "Basic
Settings" of the master station is smaller than the
cyclic transmission time calculated by the number
of stations and points of device stations set in
"Network Configuration Settings" under "Basic
Settings".
Set the value of "Cyclic Transmission Time" as a value equal to or
larger than the value of "Cyclic Transmission Time (Calculation
value)" (SW0073) of a local station using "Communication Period
Setting" under "Basic Settings" of the master station. ( Page 286
Communication cycle intervals)
If the same error occurs again even after taking the above, please
consult your local Mitsubishi representative.
3018H The value set in "Transient Transmission Time" in
"Communication Period Setting" under "Basic
Settings" of the master station is smaller than the
transient transmission time calculated using the
number of device stations and the points of device
stations set in "Network Configuration Settings"
under "Basic Settings".
Set "Communication Period Interval Setting" and "Cyclic
Transmission Time" so that the value of "Transient Transmission
Time" in "Communication Period Setting" under "Basic Settings" of
the master station is equal to or larger than the value of "Transient
Transmission Time (Calculation value)" (SW0078) of a local station.
( Page 286 Communication cycle intervals)
If the same error occurs again even after taking the above, please
consult your local Mitsubishi representative.
Error
code
Error definition and causes Action Detailed
information 1
Detailed
information 2

Table of Contents