72
5 SYSTEM CONFIGURATION
5.1 Structure of CC-Link IE TSN Class B Devices and Ethernet Devices
Connection with modules on CC-Link IE TSN with a communication speed of 100Mbps
The following shows the network topologies when a CC-Link IE TSN module with a communication speed of 100Mbps is
connected.
Line topology
The communication speed of the module must be adjusted for connection. (When connecting modules with different
communication speeds, an industrial switch (for CC-Link IE TSN Class B) is required.)
Star topology
The network is configured in a star topology via an industrial switch.
When the master station with a communication speed of 1Gbps and a remote station with a communication speed of
100Mbps exist in the structure, set "Communication Period Setting" to "Low-Speed" for the remote station with a
communication speed of 100Mbps.
The same communication speed must be set for the master station and local station.
No.0: Master station
No.1, No.3: Remote station
No.2: Local station
No.0: Master station
No.1: Local station
No.2, No.3: Remote station
No.0: Master station
No.1, No.3: Local station
No.2: Remote station
No.0
100Mbps
No.1
100Mbps
No.3
100Mbps
p
No.2
100Mbps
No.0 (1Gbps)
No.1
(1Gbps)
No.2 (100Mbps)
No.3 (100Mbps)
No.0 (1Gbps)
No.1
(1Gbps)
No.2 (100Mbps)
No.3 (100Mbps)
Low
speed
Low
speed
Low
speed
Basic
cycle
Industrial switch
(for CC-Link IE
TSN Class B)
Industrial switch
(for CC-Link IE
TSN Class B)
No.0 (1Gbps)
No.1
(100Mbps)
No.2 (100Mbps)
No.3
(100Mbps)
No.0 (100Mbps)
No.1
(100Mbps)
No.2 (100Mbps)
No.3
(100Mbps)
Industrial switch
(for CC-Link IE
TSN Class B)
Industrial switch
(for CC-Link IE
TSN Class B)

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-F Series

Related product manuals