74
5 SYSTEM CONFIGURATION
5.1 Structure of CC-Link IE TSN Class B Devices and Ethernet Devices
• When the communication speed of the master station is 1Gbps, a connection cannot be established if the total cyclic data
size of all device stations on the 100Mbps device side exceeds 2K bytes. This includes the devices with a communication
speed of 100Mbps that form a boundary between the communication speed of 1Gbps and 100Mbps.
No.0: Master station
No.1, No.10: Local station
No.2, No.3, No.4, No.5, No.6, No.7, No.8, No.9: Remote station
Set the total cyclic data size within 2K bytes.
No.1
(1Gbps)
No.3
(1Gbps)
No.2
(1Gbps)
No.8
(100Mbps)
No.7
(100Mbps)
No.9
(100Mbps)
No.0
(1Gbps)
No.10
(1Gbps)
No.5
(100Mbps)
No.6
(100Mbps)
No.4
(100Mbps)
Ò
Ò
Industrial switch
(for CC-Link IE
TSN Class B)
Industrial switch
(for CC-Link IE
TSN Class B)