5 SYSTEM CONFIGURATION
5.1 Structure of CC-Link IE TSN Class B Devices and Ethernet Devices
When the communication speed of the master station is 1Gbps, a connection cannot be established if the total cyclic data
size of all device stations on the 100Mbps device side exceeds 2K bytes. This includes the devices with a communication
speed of 100Mbps that form a boundary between the communication speed of 1Gbps and 100Mbps.
No.0: Master station
No.1, No.10: Local station
No.2, No.3, No.4, No.5, No.6, No.7, No.8, No.9: Remote station
Set the total cyclic data size within 2K bytes.