5 SYSTEM CONFIGURATION
5.3 Structure of CC-Link IE TSN Class B/A Devices (Mixture of CC-Link IE TSN Protocol Version 1.0 and 2.0) and Ethernet Devices
95
5
Operation when combined with versions of other products
The following tables show how parameters used for the FX5-CCLGN-MS operate in combination with other products that
support or do not support the CC-Link IE TSN Protocol version 2.0.
Combination with the engineering tool
"CC-Link IE TSN Class Setting" for each device station in the "CC-Link IE TSN Configuration" window of the "Network
Configuration Settings"
Multiplier setting for "Low-Speed" in "Multiple Period Setting" under "Basic Settings"
"TSN HUB Setting" in "Connection Device Information" under "Basic Settings"
Precautions
If parameters are written with an engineering tool of software version "1.085P" or later for a project created with an
engineering tool of software version earlier than "1.085P" without opening "Network Configuration Settings" once, the module
operates with the CC-Link IE TSN Protocol version 1.0.
Combination with a device station
When a CC-Link IE TSN Class A device that supports CANopen profile with the CC-Link IE TSN Protocol version 2.0 is
connected, use the FX5-CCLGN-MS with the firmware version "1.020" or later.
CC-Link IE TSN Protocol version 2.0 support Operation
Engineering tool Module
Not supported Not supported CC-Link IE TSN Protocol version 1.0
Supported CC-Link IE TSN Protocol version 1.0
Supported Not supported CC-Link IE TSN Protocol version 1.0
Supported CC-Link IE TSN Protocol version 1.0/2.0
CC-Link IE TSN Protocol version 2.0 support Operation
Engineering tool Module
Not supported Not supported Only "16" settable
Supported Only "16" settable
Supported Not supported A value other than "16" results in a network
parameter error (error code: 2221H)
Supported "16", "32", "64", or "128" selectable
CC-Link IE TSN Protocol version 2.0 support Operation
Engineering tool Module
Not supported Not supported Setting not allowed
Supported Setting not allowed
Supported Not supported CC-Link IE TSN Protocol version 1.0 regardless of
the setting value
Supported Operate according to the setting value